No, all are separate modules for DI – DO – AO – AI

Yes. all 16 digital inputs have 32 bit counters with UP/Down counting feature. and it also supports storage of counters during power OFF. so values are retained

15 Modbus Slave devices can connect on RS-485 Master Port. Two RS-485 ports available. one port active at a time

All Standard MINT IOs are having 2 RS485 Modbus RTU Slave available. Ethernet model having one MODBUS TCP/IP port and one RS485 MODBUS RTU slave port available

0/4-20mA and 0/2- 10VDC outputs are available. both models are separate models.

MINT-AO-I

MINT-AO-V

Yes. only in Current and Voltage Inputs. -2000 to 20000 Counts

Outdoor range- Clear Line Of Site without Obstacles > 1Km

Upto 256. 247 IOs with 8 Repeaters after every 31 MINT IOs in a single RS-485 loop

120 ohm Termination resistor is available via switch selection on the front of IO.

Switch No. 9 for RS-485 Port-1/Switch No.10 for RS-485 Port-2

No but 3 Ports Isolation is available. 1500 VAC for 1 Min

1> Power Supply to Field IO

2> Power supply to Communication Ports

3> Communication Ports to Field IO signals

No but 3 Ports Isolation is available. 1500 VAC for 1 Min

1> Power Supply to Field IO

2> Power supply to Communication Ports

3> Communication Ports to Field IO signals

Source and sink both types of Open collector Outputs are available. Its Factory Set.